Abstract
In this contribution the applicability of different neural classifiers trained by sectional winding transfer functions (SWTFs) of transformer coils for evaluating wideband electrical measured partial discharges (PD) is presented and discussed. Based on PD measurements on a distribution transformer in the laboratory it is demonstrated, that the introduced technique enables beside a determination of the apparent charge an adequate localisation of the PD origin. The performance and the reproducibility of this method leads to a short outlook on planned investigations and the possibilities for integrating this technique in online condition monitoring systems.
| Original language | English |
|---|---|
| Title of host publication | Proceedings of 2001 International Symposium on Electrical Insulating Materials (ISEIM 2001) |
| Subtitle of host publication | 2001 Asian Conference on Electrical Insulation Diagnosis (ACEID 2001). 33rd Symposium on Electrical and Electronic Insulating Materials and Applications in Systems |
| Publisher | IEEE |
| Pages | 579-582 |
| Number of pages | 4 |
| ISBN (Print) | 4-88686-053-2 |
| DOIs | |
| Publication status | Published - 2001 |
| Event | International Symposium on Electrical Insulating Materials (ISEIM 2001) - Himeji, Japan Duration: 19 Nov 2001 → 22 Nov 2001 |
Conference
| Conference | International Symposium on Electrical Insulating Materials (ISEIM 2001) |
|---|---|
| Abbreviated title | ISEIM 2001 |
| Country/Territory | Japan |
| City | Himeji |
| Period | 19 Nov 2001 → 22 Nov 2001 |