In this contribution the applicability of different neural classifiers trained by sectional winding transfer functions (SWTFs) of transformer coils for evaluating wideband electrical measured partial discharges (PD) is presented and discussed. Based on PD measurements on a distribution transformer in the laboratory it is demonstrated, that the introduced technique enables beside a determination of the apparent charge an adequate localisation of the PD origin. The performance and the reproducibility of this method leads to a short outlook on planned investigations and the possibilities for integrating this technique in online condition monitoring systems.

Original languageEnglish
Title of host publicationProceedings of 2001 International Symposium on Electrical Insulating Materials (ISEIM 2001)
Subtitle of host publication2001 Asian Conference on Electrical Insulation Diagnosis (ACEID 2001). 33rd Symposium on Electrical and Electronic Insulating Materials and Applications in Systems
PublisherIEEE
Pages579-582
Number of pages4
ISBN (Print)4-88686-053-2
DOIs
Publication statusPublished - 2001
EventInternational Symposium on Electrical Insulating Materials (ISEIM 2001) - Himeji, Japan